Chapter 4 - Parameters and Menu Structure
Parameters (M3)
60 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.2.32
AI6 Filter Time
s
0
300
1
200
Defines the time it takes to reach
63% of a step change in the analog
input signal defined by AI6 Signal
Sel (P3.5.2.31).
P3.5.2.33
AI6 Signal Range
0-10V/
0-20mA
2-10V/
4-20 mA
0-10V/
0-20 mA
201
Defines the signal range for the
analog input defined by AI6 Signal
Sel (P3.5.2.31). Ranges are as
follows:
0 = 0 to 10 Vdc/0 to 20 mA
1 = 2 to 10 Vdc/4 to 20 mA
NOTE: This setting can be
bypassed by using AI6 Custom Min
(P3.5.2.34) and AI6 Custom Max
(P3.5.2.35).
P3.5.2.34
AI6 Cutom Min
%
-160
160
0
203
Defines the custom minimum to be
used for bypassing the AI6 Signal
Range (P3.5.2.33).
P3.5.2.35
AI6 Custom Max
&
-160
160
100
204
Defines the custom maximum to be
used for bypassing the AI6 Signal
Range (P3.5.2.33).
P3.5.2.36
AI6 Signal Inv
Normal
Inverted
Normal
209
Defines the operation of the analog
input 6 signal as follows:
Normal = 0V or 0 mA = 0%, 10V or
20 mA = 100%
Inverted = 0V or 0 mA = 100%, 10V
or 20 mA = 0%
Digital Outputs (M3.5.3)
The digital/relay outputs are very flexible to use. Parameters are functions/features that are connected to the
required digital/relay output terminals. The digital outputs are configured by the slot they exist on. If no expansion
board exists, then the option does not populate with data.
NOTE:
The status of the Digital/Relay Outputs can be monitored in the Multimonitor (M2.1)
view, or in the I/O and Hardware (M5) menu.
Digital outputs, slot B (Basic)
Table 33: Digital Outputs, Slot B.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.3.2.1 RO1 Function
None
Remote Start Run
11001
See
Basic RO Functions Table.
P3.5.3.2.2 RO1 ON Delay
s
0
320
0
11002
Defines the amount of time that will
pass before the relay output will
energize (ON) after trigger of the
RO1 Function (P3.5.3.2.1).
P3.5.3.2.3 RO1 OFF Delay
s
0
320
0
11003
Defines the amount of time that will
pass before the relay output will de-
energize (OFF) after trigger of the
RO1 Function (P3.5.3.2.1).