Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
161 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Quick Setup
For monitoring objects using BACnet IP, complete the following steps:
NOTICE
The DHCP settings must be set properly. Otherwise, a Fixed IP address may have to
be set up.
If using DHCP, complete the following steps:
1.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address Mode
(M5.9.1.1).
2.
Verify this is set to
DHCP with AutoIP.
3.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address (M5.9.1.2).
4.
Verify that a valid IP Address has been assigned.
If using a Fixed IP address, complete the following steps:
1.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address Mode
(M5.9.1.1) > Edit.
2.
Select
Fixed IP.
3.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address (M5.9.1.2) >
Edit.
4.
Enter the desired
IP address.
5.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Subnet Mask
(M5.9.1.3) > Edit.
6.
Enter the desired
subnet mask.
7.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Default Gateway
(M5.9.1.4) > Edit.
8.
Enter the desired
default gateway.
For either DHCP or Fixed, the following steps must be completed:
1.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > BACnet IP (M5.9.3) > Settings (M5.9.3.1) > Instance
Number (M5.9.3.1.1) > Edit.
2.
Select desired
device instance number.
3.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > BACnet IP (M5.9.3) > Settings (M5.9.3.1) > Protocol
in use (M5.9.3.1.3) > Edit.