Chapter 4 - Parameters and Menu Structure
Monitor Menu (M2)
32 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Structure
Parameter
Unit
ID
Description
M2.2.19
FireMode Status
1597
0 = Disabled
1 = Enabled
2 = Activated (Enabled & DI)
3 = Test Mode
M2.2.20
DIN StatusWord1
56
B0 = SlotA.1…B5 = SlotA.6
B6 = SlotB.1…B11 = SlotB.6
B12 = SlotC.1…B15 = SlotC.4
M2.2.21
DIN StatusWord2
57
B0 = SlotC.5…B1 = SlotC.6
B2 = SlotD.1…B7 = SlotD.6
B8 = SlotE.1…B13 = SlotE.4
M2.2.22
MotCurrent1Deci.
45
Motor current monitor value with fixed number of decimals and less filtering. For
example, can be used for fieldbus purpose to always get the right value
regardless of frame size, or monitoring when less filtering time is needed for
motor current.
M2.2.23
Appl.StatusWord1
89
Bit coded application status word 1
B0 = Interlock1
B1 = Interlock2
B5 = I/O A Control Active
B6 = I/O B Control Active
B7 = Fieldbus Control Active
B8 = Hand Control Active
B9 = PC Control Active
B10 = Preset Freq Active
B12 = FireMode Active
B13 = PreHeat Active
M2.2.24
Appl.StatusWord2
90
Bit coded application status word 2
B0 = Acc/Dec Prohibited
B1 = MotorSwitch Active
M2.2.25
kWhTripCounter Low
1054
Energy counter with kWh output (low word)
M2.2.26
kWhTripCounter High
1067
# of times energy counter has spun around (high word)
M2.2.27
Appl.StatusWord3
1851
Bit coded application status word 3
M2.2.28
Safety StatusWord
1852
Bit coded Safety Status Word
M2.2.29
Bypass Runtime
h
1850
Bypass Running Hours
Timer functions monitoring (M2.3)
The timer functions monitoring values and the actual values of the timer functions and the real time clock. See
Timer Functions
(M3.11).
Table 7: Monitoring of Timer Functions.
Structure
Parameter
Unit
ID
Description
M2.3.1
TC 1, TC 2, TC 3
1441
Status of the three time channels
M2.3.2
Interval 1
1442
Status of timer interval
M2.3.3
Interval 2
1443
Status of timer interval
M2.3.4
Interval 3
1444
Status of timer interval
M2.3.5
Interval 4
1445
Status of timer interval
M2.3.6
Interval 5
1446
Status of timer interval