Chapter 3 - Start-up Information
Wizards
26 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Step
Parameter/Question
Settings
1
Fire Mode Frequency Source (P3.16.5)
Several selections; see P3.16.5.
If Fire Mode Frequency is selected, the following will display. Otherwise, the wizard jumps directly to Step 3:
Step
Parameter/Question
Settings
2
Fire Mode Frequency (P3.16.4)
Range: 0 to Maximum Frequency (P1.9)
3
Signal Activation?
Open Contact
Closed Contact
4
Fire Mode Activation Open (P3.16.2)
Or
Fire Mode Activation Close (P3.16.3)
Choose the digital input to activate Fire Mode.
5
Fire Mode Reverse (P3.16.6)
Choose the digital input to activate the reverse command in
Fire Mode.
DigIN Slot0.1 = FORWARD
DigIN Slot0.2 = REVERSE
6
Fire Mode Password (P3.16.1)
Choose the password to enable the Fire Mode Function.:
1234 = Test Mode
1002 = Enable Fire Mode
The Fire Mode Wizard is now complete.
Bypass Wizard (P1.21)
The Bypass Wizard is activated in the Quick Setup (M1) menu. The wizard assists with configuring the drive for use
with the Conventional or Electronic Bypass options. If the Electronic Bypass option is selected, additional features
can be enabled, if desired. The standard I/O is re-mapped for use with the Electronic Bypass option. Additional
parameters are available when the Electronic Bypass option is enabled.
The following steps are required to successfully complete the Bypass Wizard:
Step
Parameter/Question
Settings
1
Select the Bypass (P3.17.4) mode
Electronic
Conventional
Disabled
If Conventional is selected, the following changes occur automatically, the wizard completes, and the message:
Bypass Wizard is now complete
.
Press OK to continue
. displays.
●
Control Signal 2 A (P3.5.1.2) is set to DigIN Slot0.1 to disable the reverse command on Digital Input 2.
●
Run Interlock 2 (P3.5.1.13) is set to DigIN SlotA.2 to enable the run interlock on Digital Input 2. The status of
the Output Contactor (M2) is factory-wired to digital input 2.
●
Preset Freq Sel0 (P3.5.1.15) is set to DigIN Slot0.1 to disable the Preset Frequency Selection 0 on Digital Input
4.
●
Overload (P3.5.1.53) is set to DigIN SlotA.5 to enable the overload on Digital Input 5. The status of the
Overload is factory-wired to Digital Input 5.
If Electronic is selected, the following change occurs automatically:
Overload (P3.5.1.53) is set to DigIN SlotA.5 to enable the overload on Digital Input 5. The status of the Overload is
factory-wired to Digital Input 5.
The wizard continues with the following steps: