Chapter 4 - Parameters and Menu Structure
Monitor Menu (M2)
30 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Structure
Parameter
Unit
ID
Description
P1.15
Ctrl. Place Auto
172
Start/Stop commands are given differently depending upon the control place.
This parameter defines whether the Start/Stop command is controlled by
digital inputs as defined in Control Signal 1 A (P3.5.1.1) and Control Signal 2
A (P3.5.1.2) in accordance with the I/O A Start/Stop Logic (P3.2.6) or if the
Start/Stop command is controlled by the Fieldbus that is in use.
Settings:
0 = I/O Control (control is from the physical I/O, PID control, or time channels)
1 = Fieldbus (control is from the configured fieldbus found in Ethernet or RS-
485 settings)
Also see
Menu Structure P3.2.1.
P1.16
Automatic Reset
731
Enable parameter for the Automatic Reset function of the drive. This feature
is configured in the Parameters (M3) … Automatic Reset (M3.10) menu.
Also see
Menu Structure P3.10.1.
P1.17
PID Mini-Wizard
1803
Enable parameter for the PID Mini-Wizard. This wizard assists with the
configuration of the PID Controller 1 using a single feedback and single
setpoint.
P1.18
MultiPump Wizard
Enable parameter for the Multi-Pump Wizard. This wizard assists with the
configuration of the Multi-Pump function of the drive. The PID Mini Wizard will
precede this wizard.
P1.19
Startup Wizard
1171
Enable parameter for the Startup Wizard. This wizard assist with the essential
information required for drive operation.
This wizard is automatically enabled after Restore Factory Defaults (P6.5.1) is
activated.
P1.20
Fire Mode Wizard
1672
Enable parameter for the Fire Mode Wizard.
P1.21
Bypass Wizard
1823
Enable parameter for the Bypass Wizard. This wizard can be activated during
the Startup Wizard.
Monitor Menu (M2)
The Siemens BT300 HVAC Drive allows you to monitor actual values, parameters, and signals as well as status
and measurements. Some of the monitored values are customizable.
Table 5: Monitor Menu.
Menu and Parameter Group
Description
Multimonitor (M2.1)
Display of 9 monitored values.
Basic (M2.2)
Display of basic drive monitoring parameters.
Timer Functions (M2.3)
Display of timer function specific monitoring parameters.
PID Controller 1 (M2.4)
Display of PID Controller 1 specific monitoring parameters.
PID Controller 2 (M2.5)
Display of PID Controller 2 specific monitoring parameters.
Multi-Pump (M2.6)
Display of Multi-Pump specific monitoring parameters.
Fieldbus Data (M2.8)
Display of Mapped Fieldbus Data monitoring parameters.
Temp. Inputs (M2.9)
Display of connected temperature inputs.
Multimonitor (M2.1)
On the Multi-Monitor page, you can collect nine values to monitor. The display fields can be changed by selecting
the display field to be changed with the
and
arrow buttons, and then pressing the
button. Scroll
Содержание BT300 LonWorks