Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
134 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Point
Number
Point
Type
Subpoint Name
Factory
Default
Engr. Units
Slope
Intercept
On Text
Off Text
Drive Menu
38
LDI
DIGITAL IN 6
OFF
ON
OFF
P5.1.6
39
LDO
RELAY OUT 1
OFF
ON
OFF
P5.1.13
40
LDO
RELAY OUT 2
OFF
ON
OFF
P5.1.14
41
LDO
RELAY OUT 3
OFF
ON
OFF
P5.1.15
42
LAO
FBDATA IN 1
0
1
0
P
43
LAO
FBDATA IN 2
0
1
0
44
LAO
FBDATA IN 3
0
1
0
45
LAO
FBDATA IN 4
0
1
0
46
LAO
FBDATA IN 5
0
1
0
47
LAO
FBDATA IN 6
0
1
0
48
LAO
FBDATA IN 7
0
1
0
49
LAO
FBDATA IN 8
0
1
0
50
LAI
FBDATA OUT 1
0
1
0
P3.6.1
51
LAI
FBDATA OUT 2
0
1
0
P3.6.2
52
LAI
FBDATA OUT 3
0
1
0
P3.6.3
53
LAI
FBDATA OUT 4
0
1
0
P3.6.4
54
LAI
FBDATA OUT 5
0
1
0
P3.6.5
55
LAI
FBDATA OUT 6
0
1
0
P3.6.6
56
LAI
FBDATA OUT 7
0
1
0
P3.6.7
57
LAI
FBDATA OUT 8
0
1
0
P3.6.8
58
LAO
PID1 GAIN
1000.00
PCT
0.1
0
P3.12.1.1
59
LAO
PID1 I TIME
10
SEC
0.1
0
P3.12.1.2
60
LAO
PID1 D TIME
0
SEC
0.1
0
P3.12.1.3
61
LAI
PID1 STATUS
0
1
0
M2.4.5
62
LAI
PID1 STPT
0
1
0
M2.4.1
63
LAI
PID1 FDBK
0
1
0
M2.4.2
64
LAI
PID1 OUTPUT
0
PCT
0.1
0
M2.4.4
65
LAO
PID 2 GAIN
1000.00
PCT
0.1
0
P3.13.1.3
66
LAO
PID2 I TIME
10.00
SEC
0.1
0
P3.13.1.4
67
LAO
PID2 D TIME
0
SEC
0.1
0
P3.13.1.5
68
LAI
PID2 STATUS
0
1
0
M2.5.5
69
LAI
PID2 STPT
0
1
0
M2.5.1
70
LAI
PID2 FDBK
0
1
0
M2.5.2
71
LAI
PID2 OUTPUT
0
PCT
0.1
0
M2.5.4
72
LAO
ANYPARM
0
1
0
73
LAO
ANYVALUE
0
1
0
74
LAI
ID VERSION
0
1
0
M4.8.6
Содержание BT300 LonWorks
Страница 1: ...Siemens BT300 HVAC Drive Operator s Manual DPD01809 Building Technologies 2016 06 07 ...
Страница 8: ......
Страница 179: ......