Table 10: Multi-Pump Monitoring.
Structure
Parameter
Unit
ID
Description
M2.6.1
Motors Running
30
The number of motors running at the moment when Multi-Pump functionality is used.
M2.6.2
Autochange
1114
If an autochange is requested,
requested means that the autochange time has elapsed
and the drive is waiting until the rest of the autochange criteria is fulfilled. For example,
output frequency of controlled drive and number of running motors.
Fieldbus data monitoring (M2.8)
The Fieldbus Data monitoring values are shown for debugging purposes. See
Fieldbus Data Mapping (M3.6).
The Fieldbus Data monitoring values are presented in the following table:
Table 11: Fieldbus Data Monitoring.
Structure
Parameter
Unit
ID
Description
M2.8.1
FB Control Word
874
Fieldbus control word used by application in bypass mode/format. Depending on the
fieldbus type or profile the data might be modified before sent to the application.
M2.8.2
FB Speed Reference Hz
875
Speed reference scaled between minimum and maximum frequency at the moment it
was received to the application. Minimum and maximum frequency might have been
changed after the reference was received without affecting the reference.
M2.8.3
FB Data In 1
876
Raw value of process data in 32-bit signed format.
M2.8.4
FB Data In 2
877
Raw value of process data in 32-bit signed format.
M2.8.5
FB Data In 3
878
Raw value of process data in 32-bit signed format.
M2.8.6
FB Data In 4
879
Raw value of process data in 32-bit signed format.
M2.8.7
FB Data In 5
880
Raw value of process data in 32-bit signed format.
M2.8.8
FB Data In 6
881
Raw value of process data in 32-bit signed format.
M2.8.9
FB Data In 7
882
Raw value of process data in 32-bit signed format.
M2.8.10
FB Data In 8
883
Raw value of process data in 32-bit signed format.
M2.8.11
FB Status Word
864
Fieldbus status word sent by application in bypass mode/format. Depending on the
fieldbus type or profile the data might be modified before sent to the fieldbus.
M2.8.12
FB Speed Actual
%
865
Actual speed in %. 0 and 100% corresponds to minimum and maximum frequency
respectively. This is continuously updated depending on the momentary min and max
frequency and output frequency.
M2.8.13
FB Data Out 1
866
Raw value of process data out 32-bit signed format.
M2.8.14
FB Data Out 2
867
Raw value of process data out 32-bit signed format.
M2.8.15
FB Data Out 3
868
Raw value of process data out 32-bit signed format.
M2.8.16
FB Data Out 4
869
Raw value of process data out 32-bit signed format.
M2.8.17
FB Data Out 5
870
Raw value of process data out 32-bit signed format.
M2.8.18
FB Data Out 6
871
Raw value of process data out 32-bit signed format.
M2.8.19
FB Data Out 7
872
Raw value of process data out 32-bit signed format.
M2.8.20
FB Data Out 8
873
Raw value of process data out 32-bit signed format.