Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
157 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Connection 2
The monitoring values display the same pieces of information as for Connection 1 [➙ 155], for the 2nd and 3rd
connections.
Connection 3
The monitoring values display the same pieces of information as for Connection 1 [➙ 155], for the 2nd and 3rd
connections.
Quick Setup
For monitoring objects using ModBus TCP, complete the following steps:
NOTICE
The DHCP settings must be set properly. Otherwise, a Fixed IP address may have to
be setup.
If using DHCP, complete the following steps:
1.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address Mode
(M5.9.1.1).
2.
Verify this is set to
DHCP with AutoIP.
3.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address (M5.9.1.2).
4.
Verify that a valid IP Address has been assigned.
If using a Fixed IP address, complete the following:
1.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address Mode
(M5.9.1.1) > Edit.
2.
Select
Fixed IP.
3.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >IP Address (M5.9.1.2) >
Edit.
4.
Enter desired
IP address.
5.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Subnet Mask
(M5.9.1.3) > Edit.
6.
Enter the desired
subnet mask.
7.
Select:
Main Menu > I/O and Hardware (M5) > Ethernet (M5.9) > Common settings (M5.9.1) >Default Gateway
(M5.9.1.4) > Edit.
8.
Enter the desired
default gateway.