Chapter 4 - Parameters and Menu Structure
Parameters (M3)
64 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
NOTE:
The status of the Analog Outputs can be monitored in the Multimonitor (P2.1) view, or
in the I/O and Hardware (M5) menu.
Slot A Basic (M3.5.4.1)
Table 38: Analog Outputs, Slot A (Basic).
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.5.4.1.1 AO1 Function
0% Test
ProcessDataIn8
Output
Frequency
10050
See
AO Functions Table.
P3.5.4.1.2 AO1 Filter Time
s
0
300
1
10051
Filter time of analog output signal
0 = No filtering
P3.5.4.1.3 AO1 Min Signal
0 Vdc/0 mA 2 Vdc/4 mA
0 Vdc/0 mA
10052
Settings:
0 = 0 Vdc/0 mA
1 = 2 Vdc/4 mA
P3.5.4.1.4 AO1 MinScale
Varies
Varies
Varies
10053
Min Scale in process unit.
P3.5.4.1.5 AO1 MaxScale
Varies
Varies
Varies
10054
Max Scale in process unit
Table 39: Analog Output Functions.
Settings
Description
0
0% Test
AO is not used. 0 output.
1
100% Test
AO is max. 10 Vdc or 20 mA output.
2
Output Frequency
Track the Output Frequency based on 0 to Max Frequency (P3.3.2).
3
Freq Reference
Track the Frequency Reference base on 0 to Max Frequency (P3.3.2).
4
Motor Speed
Track the Motor Speed based on 0 to Motor Nom Speed (P3.1.1.3).
5
Output Current
Track the Output Current based on 0 to Motor Nom Currnt (P3.1.1.4).
6
Motor Torque
Track the Motor Torque based on 0 to TnMotor.
7
Motor Power
Track the Motor Power based on 0 to PnMotor.
8
Motor Voltage
Track the Motor Voltage based on 0 to VnMotor.
9
DC Link Voltage
Track the DC Link Voltage based on 0 - 1000 Vdc.
10
PID 1 Output
Track the PID1 Output based on 0 - 100%
11
PID 2 Output
Track the PID2 Output based on 0 - 100%.
12
Process Data In 1
Track the Process Data In 1 where 5000 = 50.00%.
13
Process Data In 2
Track the Process Data In 2 where 5000 = 50.00%.
14
Process Data In 3
Track the Process Data In 3 where 5000 = 50.00%.
15
Process Data In 4
Track the Process Data In 4 where 5000 = 50.00%.
16
Process Data In 5
Track the Process Data In 5 where 5000 = 50.00%.
17
Process Data In 6
Track the Process Data In 6 where 5000 = 50.00%.
18
Process Data In 7
Track the Process Data In 7 where 5000 = 50.00%.
19
Process Data In 8
Track the Process Data In 8 where 5000 = 50.00%.
Содержание BT300 LonWorks
Страница 1: ...Siemens BT300 HVAC Drive Operator s Manual DPD01809 Building Technologies 2016 06 07 ...
Страница 8: ......
Страница 179: ......