Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
120 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Table 90: N2 Analog Inputs.
NPT
NPA
Description
Units
Note
AI
1
Speed Setpoint
Hz
2 decimal places
AI
2
Output Frequency
Hz
2 decimal places
AI
3
Motor Speed
RPM
0 decimal places
AI
4
Load (power)
%
1 decimal
AI
5
Megawatt Hours
MWh
Total counter
AI
6
Motor Current
A
2 decimal places
AI
7
Bus Voltage
V
0 decimal places
AI
8
Motor Volts
V
1 decimal place
AI
9
Heatsink Temperature
°C
0 decimal places
AI
10
Motor Torque
%
1 decimal place
AI
11
Operating Days (trip)
Day
0 decimal places
AI
12
Operating Hours (trip)
Hour
0 decimal places
AI
13
Kilowatt Hours (trip)
kWh
Trip Counter
AI
14
Torque Reference
%
1 decimal place
AI
15
Motor Temperature Rise
%
1 decimal place
AI
16
FBProcessDataOut1*
0 decimal places
AI
17
FBProcessDataOut2*
0 decimal places
V
18
FBProcessDataOut3*
0 decimal places
V
19
FBProcessDataOut4*
0 decimal places
AI
20
FBProcessDataOut5*
0 decimal places
AI
21
FBProcessDataOut6*
0 decimal places
AI
22
FBProcessDataOut7*
0 decimal places
AI
23
FBProcessDataOut8*
0 decimal places
Binary Inputs (BI)
All binary inputs (BI) points have the following features:
●
Support Change of State (COS) reporting based on current state.
●
Support Change of State (COS) reporting based on alarm condition.
●
Support Change of State (COS) reporting based on override status.
●
Always considered reliable.
●
Overriding is supported from the standpoint that the “Override Active” bit will be set and the value reported to
the N2 network will be the overridden value. However, the value in the drive remains unchanged. Therefore,
the N2 system should be set up to disallow overriding BI point or have an alarm condition activated when a BI
point is overridden.
Table 91: N2 Binary Inputs.
NPT
NPA
Description
0 =
1 =
BI
1
Ready
Not Ready
Ready
BI
2
Run
Stop
Run
BI
3
Direction
Clockwise
Counterclockwise