Chapter 4 - Parameters and Menu Structure
Parameters (M3)
68 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.6.8
FB DataOut 8 Sel
0
35000
Last Fault (37)
859
Defines the data to be sent to the
fieldbus as FB DataOut 8. See
FBDataOut 1 Sel (P3.6.1) for
further details.
BACnet = AV_27
P1 = Subpoint 57
P3.6.9
FB Run Enable
Disabled Enabled Enabled
1829
Defines the run enable when in
fieldbus control.
NOTE: When fieldbus is not in use,
see Run Enable (P3.5.1.11)
For example, to provide the PID1 Feedback over the fieldbus. Complete the following:
Set Fieldbus Data Out 1 Selection (P3.6.1) can be set to a value of 21 [which represents PID Feedback (P2.4.2)].
Содержание BT300 LonWorks
Страница 1: ...Siemens BT300 HVAC Drive Operator s Manual DPD01809 Building Technologies 2016 06 07 ...
Страница 8: ......
Страница 179: ......