Protections (M3.9)
Protections define the way the drive is to respond to conditions that can occur in the drive.
Table 46: Protections Settings.
Structure
Parameter
Unit
Min
Max
Default
ID
Description
P3.9.1
AI Low Fault
No Action
Fault, Coast No Action
700
Defines the response to a low analog input
signal. Response settings are as follows:
0 = No Action
1 = Alarm
2 = Alarm and run to PresetAlarmFreq
(P3.3.19)
3 = Fault
(stop according to stop mode)
4 = Fault
(stop by coasting)
P3.9.2
External Fault
No Action
Fault, Coast Fault
701
Defines the response to activation of an
Ext Fault Close (P3.5.1.7) or Ext Fault
Open (P3.5.1.8). Response settings are as
follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
P3.9.3
InputPhaseFault
3-phase
1-phase
3-phase
730
Defines the input phase support.
0 = 3-phase support
1 = 1-phase support
NOTE
: If single phase supply is used, 1-
phase support must be selected.
P3.9.4
Undervoltage Flt
Fault Stored No History
Fault Stored 727
Defines if the under-voltage fault is stored
in the fault history or not.
0 = Fault Stored
1 = No History
P3.9.5
OutputPhase Flt
No Action
Fault, Coast Fault
702
Defines the response to an output phase
loss. Response settings are as follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
P3.9.6
Motor Therm Prot
No Action
Fault, Coast Fault
704
Defines the response to a motor thermal
protection. Response settings are as
follows:
0 = No Action
1 = Alarm
2 = Fault
(stop according to stop mode)
3 = Fault
(stop by coasting)
P3.9.7
MotAmbient Temp
ºF
-4
212
104
705
Defines the ambient temperature that is to
generate a response to a Motor Thermal
Protection fault as defined by Motor Therm
Prot (P3.9.6.
P3.9.8
ZeroSpeedCooling
%
5
150
60
706
Defines the cooling factor at zero speed in
relation to the point where the motor is
running at nominal speed without external
cooling.
P3.9.9
ThermTimeConst
min
1
200
Varies
707
The time constant is the time within which
the calculated thermal stage has reached
63% of its final value.
P3.9.10
MotThermLoadbil
%
0
150
100
708
Motor thermal loadability states how much
the motor can be thermally loaded.