Chapter 4 - Parameters and Menu Structure
Favorites (M7)
163 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
Table 135: Parameter Backup.
Structure
Parameter
ID
Description
P6.5.1
Restore Factory
Default
831
Activation parameter for restoring parameters to the factory settings.
NOTE: Does not reset: Time (P5.5.2), Date (P5.5.3), Year (P5.5.4), Daylight Saving (P5.5.5)
P6.5.2
Save to Keypad
2487
Initiates a copy of the active set of parameters to the keypad's storage location.
P6.5.3
Restore from Keypad 2488
Initiates a copy of the keypad's storage location to the active set of parameters.
P6.5.4
Save to Set 1
2489
Initiates a copy of the active set of parameters to the drives set 1 storage location.
P6.5.5
Restore from Set 1
2490
Initiates a copy of the drives set 1 storage location to the active set of parameters.
P6.5.6
Save to Set 2
2491
Initiates a copy of the active set of parameters to the drives set 2 storage location.
P6.5.7
Restore from Set 2
2492
Initiates a copy of the drives set 2 storage location to the active set of parameters.
Parameter Compare (M6.6)
The keypad can be used to compare the drive’s active set of parameters to default values, stored sets on the drive,
and the stored set on the keypad. See the
Parameter Backup (6.5)
section for details on how to back up and
restore using these sets.
Table 136: Parameter Compare (M6.6).
Structure
Parameter
ID
Description
P6.6.1
Active Set-Set 1
2493
Initiates a compare of the drive‘s active parameter set to the saved set 1. All
parameters that are different are displayed, with values.
P6.6.2
Active Set-Set 2
2494
Initiates a compare of the drive‘s active parameter set to the saved set 2. All
parameters that are different are displayed, with values.
P6.6.3
Active Set-Defaults
2495
Initiates a compare of the drive‘s active parameter set to the default values. All
parameters that are different are displayed, with values.
P6.6.4
Active Set-Keypad Se
2496
Initiates a compare of the drive‘s active parameter set to the keypad saved set. All
parameters that are different are displayed, with values.
Favorites (M7)
Favorites are typically used to collect a set of commonly referred to sets of parameters or monitoring signals from
any of the keypad menus. Items can be added to the Favorites folder by selecting the Add To Favorites option.
To remove an item from the Favorites menu, select the item in the Favorites menu, and then select the Rem from
Favorites option.
User Levels (M8)
User level parameters are intended to restrict the visibility of parameters and prevent the unauthorized and
inadvertent parameterization on the keypad.
To lock the keypad from unauthorized changes, complete the following steps:
1.
Set Access Code (P8.2) to a value other than 0.
NOTE:
Store this access code in a safe place. If the code is lost, the only method to recover
is to reload firmware and re-commission the drive.
Содержание BT300 LonWorks
Страница 1: ...Siemens BT300 HVAC Drive Operator s Manual DPD01809 Building Technologies 2016 06 07 ...
Страница 8: ......
Страница 179: ......