Chapter 4 - Parameters and Menu Structure
I/O and Hardware (M5)
145 | 180
Siemens Industry, Inc.
Siemens BT300 HVAC Drive
DPD01809
Building Technologies
2016-06-07
ID Map
Using the ID map, you can read consecutive memory blocks that contain parameters whose IDs are not in a
consecutive order. The address range 10501 through 10530 is called
IDMap
, and includes an address map in
which you can write your parameter IDs in any order. The address range 10601 through 10630 is called
IDMap
Read/Write
, and includes values for parameters written in the ID map. As soon as one ID number has been written
in the map cell 10501, the corresponding parameter value can be read and written in the address 10601, and so
on.
Table 119: ID Map Initialization.
Once the IDMap address range has been initialized with any parameter ID number, the parameter value can be
read and written in the IDMap Read/Write address range address IDMap a 100.
Table 120: Parameter Values in 16-bit IDMap Read/Write Registers.
Address
Data
410601
Data included in parameter ID700
410602
Data included in parameter ID702
410603
Data included in parameter ID707
410604
Data included in parameter ID704
If the IDMap table has not been initialized, all fields show the index 0. If it has been initialized, the parameter IDs
included in it are stored in the flash memory of the OPT-CI board.
Address
Data
Parameter ID
’s
10501
10502
10503
10504
700
702
707
704
ID
699
700
701
702
703
704
705
706
707
708
9328.emf
Содержание BT300 LonWorks
Страница 1: ...Siemens BT300 HVAC Drive Operator s Manual DPD01809 Building Technologies 2016 06 07 ...
Страница 8: ......
Страница 179: ......