- 135 -
Event output EV1
Output turns ON or OFF, depending on Event condition selected in
[Event output EV1 allocation].
Event output EV2
Output turns ON or OFF, depending on Event condition selected in
[Event output EV2 allocation].
Disabled if the D
option is ordered.
Event outputs EV3, EV4
Output turns ON or OFF, depending on Event condition selected in
[Event output EV3 allocation] or [Event output EV4 allocation].
Event output EV3 and EV4 share one common terminal.
Alarm action
High limit alarm, High limit with standby alarm, Low limit alarm, Low limit
with standby alarm, High/Low limits alarm, High/Low limits with standby
alarm, High/Low limit range alarm, High/Low limit range with standby
alarm, Process high alarm, Process high with standby alarm, Process
low alarm, Process low with standby alarm
Alarm Energized/De-energized action are applied to the above alarms,
totaling 24 alarm types. No alarm action can also be selected.
Set value
Factory default value: 0
Action
ON/OFF action
Alarm hysteresis
0.1 to 1000.0
( )
DC voltage, current input: 1 to 10000 (The placement of the decimal
point follows the selection.)
Output
EV
output for which Alarm output (001 to 012) is selected in [Event
output EV
allocation].
Loop break alarm
When Loop break alarm is selected in [Event output EV
allocation],
detects actuator trouble (heater burnout, heater adhesion) or sensor
burnout.
Loop break alarm time
0 to 200 minutes
Loop break alarm span
Thermocouple, RTD input without decimal point: 0 to 150
( )
Thermocouple, RTD input with decimal point: 0.0 to 150.0
( )
DC voltage, current input: 0 to 1500 (The placement of the decimal
point follows the selection.)
Output
EV
output for which Loop break alarm output (014) is selected in
[Event output EV
allocation].
Event input
Select a pattern from 1 – 15 depending on ON (Closed) or OFF (Open)
status of any terminal (DI1 to DI4) and the COM terminal.
If Serial communication (C or C5 option) is ordered, only Event input
DI1 and DI2 can be used, and a pattern from 1 – 3 can be selected to
perform.
Pattern number selected by Event input has priority over Pattern
number selected by the
key.
To select pattern numbers by keypad, make sure all Event inputs are in
OFF (Open) status.
Level action is used to determine ON or OFF.
When power is turned ON, level action is engaged.
External operation input
By detecting signal edge action from OFF (Open) to ON (Closed),
program control can be performed, stopped, held or advanced.
During Manual control, External operation input will be disabled.
Signal edge action is used to determine OFF or ON.
When power is turned ON, level action is engaged.
Data clear function
When program control is stopped (in Standby), and if the
,
and
keys are pressed for approx. 3 seconds, the PV Display indicates
, and all setting values – except Input type, OUT1 proportional
cycle, OUT2 proportional cycle – will return to the default value. It takes
approximately 30 seconds for data clear.