- 158 -
12.12 Input Parameter Setting Group
Upper left: PTN Display, PV Display
The PTN Display is unlit, and the PV Display indicates setting item characters.
Lower left: STEP Display, SV/MV/TIME Display
The STEP Display is unlit, and the SV/MV/TIME Display indicates factory default value.
Right side: Indicates the setting item and setting range.
Character,
Factory Default
Setting Item, Setting Range
Data
Input type
: K -200 to 1370
: K -200.0 to 400.0
: J -200 to 1000
: R 0 to 1760
: S 0 to 1760
: B 0 to 1820
: E -200 to 800
: T -200.0 to 400.0
: N -200 to 1300
: PL-
0 to 1390
: C(W/Re5-26) 0 to 2315
: Pt100 -200.0 to 850.0
: JPt100 -200.0 to 500.0
: Pt100 -200 to 850
: JPt100 -200 to 500
: Pt100 -100.0 to 100.0
: Pt100 -100.0 to 500.0
: K -328 to 2498
: K -328.0 to 752.0
: J -328 to 1832
: R 32 to 3200
: S 32 to 3200
: B 32 to 3308
: E -328 to 1472
: T -328.0 to 752.0
: N -328 to 2372
: PL-
32 to 2534
: C(W/Re5-26) 32 to 4199
: Pt100 -328.0 to 1562.0
: JPt100 -328.0 to 932.0
: Pt100 -328 to 1562
: JPt100 -328 to 932
: Pt100 -148.0 to 212.0
: Pt100 -148.0 to 932.0
: 4 to 20 mA DC -2000 to 10000
: 0 to 20 mA DC -2000 to 10000
: 0 to 10 mV DC -2000 to 10000
: -10 to 10 mV DC -2000 to 10000
: 0 to 50 mV DC -2000 to 10000
: 0 to 100 mV DC -2000 to 10000