- 150 -
12.5 Time Signal Block Setting Group
Upper left: PTN Display, PV Display
The PTN Display is unlit, and the PV Display indicates setting item characters.
Lower left: STEP Display, SV/MV/TIME Display
The STEP Display is unlit, and the SV/MV/TIME Display indicates factory default value.
Right side: Indicates the setting item and setting range.
Character,
Factory Default
Setting Item, Setting Range
Data
Block 0 Time signal output OFF time
00:00 to 99:59
Time unit follows the selection in [Step time unit].
Block 0 Time signal output ON time
00:00 to 99:59
Time unit follows the selection in [Step time unit].
Block 1 Time signal output OFF time
00:00 to 99:59
Time unit follows the selection in [Step time unit].
Repeat the above settings up to ‘Block 15 Time signal output ON time’,
in the same way if necessary.
Block 15 Time signal output ON time
00:00 to 99:59
Time unit follows the selection in [Step time unit].