6.2 Initial Setting, Program Pattern Setting and Block Setting
• Example of Initial Setting
Setting Group
Setting Item
Setting Example
Input parameter
setting group
Input type
K, -200 to 1370
Scaling high limit
1200
Scaling low limit
0
Output parameter
setting group
OUT1 proportional cycle
15 seconds
Direct/Reverse action
Reverse action
Event output parameter
setting group
Event output EV2 allocation
Process high alarm
EV2 alarm Energized/
De-energized
Energized
Other parameters
setting group
Program start Auto/Manual
Manual start
Program control start type
PV start
Power restore action
Continues after power is
restored
Step time unit
Hours:Minutes
Step time indication
Remaining time
Step SV indication
SV corresponding to the step
time progress
Step SV Hold function when
program ends
Not holding
• Example of Program Pattern Setting
Pattern 1
Step number
0
1
2
3
4
Step SV
500
500
1000
1000
0
Step time
0:30
1:00
0:40
1:00
2:00
PID block number
1
1
2
2
1
Wait block number
1
0
1
0
0
Alarm block number
1
2
1
2
1
Output block number
0
1
0
1
0
(Fig. 6.2-1)
0
500
1000