- 82 -
Character,
Factory Default
Setting Item, Function, Setting Range
Loop break alarm span
• Sets the action span to assess the Loop break alarm.
• Setting range:
Thermocouple, RTD input without decimal point: 0 to 150
( )
Thermocouple, RTD input with decimal point: 0.0 to 150.0
( )
DC voltage, current input: 1 to 1500
(The placement of the decimal point follows
the selection.)
Available when 014 (Loop break alarm output) is selected in [Event output EV4
allocation].
At this stage, settings of Event output parameter setting group are complete.
If the
and
keys are pressed at the same time, the unit returns to the Engineering setting
group.
By pressing the
key, the unit returns to RUN mode.