- 89 -
Character,
Factory Default
Setting Item, Function, Setting Range
Step time unit
• Selects the Step time unit.
• Selection item:
: Hours:Minutes
: Minutes:Seconds
Step time indication
• During program control, selects step time indication type
when the SV/MV/TIME Display is switched to TIME indication.
• Selection item:
: Remaining time
Indicates remaining step time.
: Step time
Indicates step time which has been set.
Step SV indication
• During program control, selects step SV indication type
when the SV/MV/TIME Display is switched to SV indication.
• Selection item:
: SV corresponding to the step time progress.
Updates step SV corresponding to the step time progress.
: Step SV
Indicates the step SV which has been set during program
pattern setting.
Pattern end output time
• Sets Pattern end output time after program control is finished.
If Pattern end output is selected in [Event output EV
allocation], pattern
end output is turned ON after program control is finished, and the
SV/MV/TIME Display flashes
.
Setting the time to 0 (zero) seconds causes continuous output, until the
key is pressed for 1 second, or until the power is turned OFF.
By pressing the
key for 1 second, Pattern end output is turned OFF,
and the unit returns to Program control Stop (in Standby).
When set to 1 to 10000 seconds: Pattern end output is automatically turned
OFF after Pattern end output time has elapsed, and the unit returns to
Program control Stop (in Standby).
• Setting range:
0 to 10000 seconds