- 70 -
Character,
Factory Default
Setting Item, Function, Setting Range
• Selection item:
: Air cooling (Linear characteristics)
: Oil cooling (1.5th power of the linear characteristics)
: Water cooling (2nd power of the linear characteristics)
Available when Heating/Cooling control (DR, DS or DA option) is ordered.
OUT2 ON/OFF hysteresis
• Sets OUT2 ON/OFF hysteresis.
(Fig. 7.5.2-3)
• Setting range:
Thermocouple, RTD input: 0.1 to 1000.0
( )
DC voltage, current input: 1 to 10000
(The placement of the decimal point follows
the selection.)
Available when Heating/Cooling control (DR, DS or DA option) is ordered.
Overlap/Dead band
• Sets the overlap band or dead band for OUT1 and OUT2.
+ Set value: Dead band
– Set value: Overlap band
[Overlap band]
(Fig. 7.5.2-4)
ON
Hysteresis
OFF
OUT2 hysteresis
SV
OUT1 proportional band
ON
OFF
SV
OUT2 proportional band
Overlap band
OUT1
OUT2
ON
OFF