7.5.6 Communication Parameter Setting Group
In Communication parameter setting group, the following can be set:
Communication protocol, Instrument number, Communication speed, Response delay time, etc.
Setting items in the Communication parameter setting group are shown below.
Available when Serial communication (C or C5 option) are ordered.
Character,
Factory Default
Setting Item, Function, Setting Range
Communication protocol
• Selects communication protocol.
• Selection item:
: Shinko protocol
: Modbus ASCII
: Modbus RTU
: Set value (SV) digital transmission
Instrument number
• Sets the instrument number.
The instrument numbers should be set one by one when multiple
instruments are connected in Serial communication, otherwise
communication is impossible.
• Setting range:
0 to 95
Communication speed
• Selects a communication speed equal to that of the host computer.
• Selection item:
: 9600 bps
: 19200 bps
: 38400 bps
Data bit/Parity
• Selects data bit and parity, in accordance with the data bit and parity of the
host computer.
• Selection item:
: 8 bits/No parity
: 7 bits/No parity
: 8 bits/Even
: 7 bits/Even
: 8 bits/Odd
: 7 bits/Odd
Stop bit
• Selects the stop bit, in accordance with the stop bit of the host computer.
• Selection item:
: 1 bit
: 2 bits