- 71 -
Character,
Factory Default
Setting Item, Function, Setting Range
[Dead band]
(Fig. 7.5.2-5)
• Setting range:
Thermocouple, RTD input: -200.0 to 200.0
( )
DC voltage, current input: -2000 to 2000
(The placement of the decimal point
follows the selection.)
Available when Heating/Cooling control (DR, DS or DA option) is ordered.
Direct/Reverse action
• Selects either Reverse (Heating) or Direct (Cooling) control action.
• Selection item:
: Reverse action
: Direct action
At this stage, settings of Output parameter setting group are complete.
If the
and
keys are pressed at the same time, the unit returns to the Engineering setting
group.
By pressing the
key, the unit returns to RUN mode.
ON
OFF
OUT1
OUT1 proportional band
OUT2 proportional band
Dead band
OUT2
SV
ON
OFF