- 11 -
Action Indicator (Backlight: Orange)
No.
Name
Description
⑪
OUT1
Lit when control output OUT1 is ON.
For direct current output type, flashes corresponding to the MV
in 125 ms cycles.
OUT2
Lit when control output OUT2 (DR, DS or DA option) is ON.
For direct current output type (DA option), flashes corresponding to the
MV in 125 ms cycles.
EVT1
Lit when Event output EV1 is ON.
EVT2
Lit when Event output EV2 is ON.
EVT3
Lit when Event output EV3 is ON.
EVT4
Lit when Event output EV4 is ON.
MAN
Lit when Manual control is performing.
T/R
Lit during Serial communication (C or C5 option) TX (transmitting) output.
AT
Flashes during AT (Auto-tuning).
Lit in AT standby when ‘Multi mode’ is selected in [AT mode].
LOCK
Lit when ‘Lock’ is selected in [Set value lock].
RUN
Lit during program control RUN.
Flashes during Fixed value control.
HOLD
Flashes during program control HOLD.
Key
No.
Name
Description
⑫
RUN key
Performs program control.
Cancels HOLD during Program control HOLD.
⑬
PATTERN/UP key
PATTERN key: Selects program pattern number.
UP key: Increases the numerical value in setting mode.
⑭
SET/RESET key
SET key: Moves to setting mode.
RESET key: Moves to RUN mode.
⑮
STOP/MODE key
STOP key: Stops the program control, or cancels the pattern end output.
MODE key: Switches or selects setting mode.
⑯
ADVANCE/DOWN
key
ADVANCE key: During program control, interrupts performing step, and
proceeds to the next step (ADVANCE function).
DOWN key: Decreases the numerical value in setting mode.
⑰
FAST key
During program control, makes step time progress 60 times faster.
In setting mode, makes the numerical value change faster.
⑱
HOLD/ENTER
key
HOLD key: During program control, time progress pauses, and control
continues with the SV at the given time (HOLD function).
ENTER key: Registers the setting data, and moves to the next setting
item.
⑲
DISPLAY/
BACK MODE key
DISPLAY key: Switches the indication on the SV/MV/TIME Display.
BACK MODE key: Moves back to the previous mode.
Console Connector
No.
Name
Description
⑳
Console
connector
By connecting the USB communication cable (CMB-001, sold separately),
the following operations can be conducted from an external computer,
using the Console software SWC-PCA01M.
• Reading and setting of SV, PID and various set values
• Reading of PV and action status
• Function change
Содержание PCA1
Страница 1: ...PROGRAMMABLE CONTROLLER PCA1 INSTRUCTION MANUAL ...
Страница 9: ... 9 2 Name and Functions of Controller Fig 2 1 ...
Страница 179: ... 179 ...