- 165 -
Character,
Factory Default
Setting Item, Setting Range
Data
EV4 alarm hysteresis
Thermocouple, RTD input: 0.1 to 1000.0
( )
DC voltage, current input: 1 to 10000
(The placement of the decimal point
follows the selection.)
Available when 001 to 012 (Alarm output) is selected in [Event output EV4
allocation].
EV4 alarm delay time
0 to 10000 seconds
Available when 001 to 012 (Alarm output) is selected in [Event output EV4
allocation].
EV4 alarm Energized/De-energized
: Energized
: De-energized
Available when 001 to 012 (Alarm output) is selected in [Event output EV4
allocation].
Loop break alarm time
0 to 200 minutes
[Setting to 0 (zero) disables the Loop break alarm.]
Available when 014 (Loop break alarm output) is selected in [Event output EV4
allocation].
Loop break alarm span
Thermocouple, RTD input without decimal point: 0 to 150°C (°F)
Thermocouple, RTD input with decimal point: 0.0 to 150.0°C (°F)
DC voltage, current input: 1 to 1500
(The placement of the decimal point
follows the selection.)
Available when 014 (Loop break alarm output) is selected in [Event output EV4
allocation].