- 133 -
Setting Structure
Function key
RUN key
Performs program control.
Cancels HOLD during Program control HOLD.
PATTERN key
Selects program pattern number.
UP key
Increases the numeric value in setting mode.
FAST key
During program control, makes step time progress
60 times faster.
In setting mode, makes the numeric value change
faster.
ADVANCE key
During program control, interrupts performing
step, and proceeds to the next step (Advance
function).
DOWN key
Decreases the numeric value in setting mode.
SET key
Moves to setting mode.
RESET key
Moves to RUN mode.
STOP key
Stops the program control, or cancels the pattern
end output.
MODE key
Switches or selects setting mode.
DISPLAY key
Switches the indication on the SV/MV/TIME
Display.
BACK MODE key
Moves back to the previous mode.
HOLD key
During program control, time progress pauses,
and control continues using the SV at the given
time (HOLD function).
ENTER key
Registers the setting data, and moves to the next
setting item.
Program Performance
Number of patterns
16 (Linkable)
Number of steps
256 (16 steps/pattern)
Number of repetitions
0 to 9999 times (Repetitions disabled when set to 0)
Program time range
0 to 99 hours 59 minutes/step, or 0 to 99 minutes 59 seconds/step
(When
is set: Fixed value control is performed using step SV.)
Wait value
Thermocouple, RTD input without decimal point:
(0 to 100)
( )
Thermocouple, RTD input with decimal point:
(0.0 to 100.0)
( )
DC voltage, current input:
(0 to 1000)(The placement of the decimal
point follows the selection.)
(The Wait function is disabled when set to 0 or 0.0.)
Control Performance
Control action
• PID control action (with AT function)
• ON/OFF control action (When proportional band is set to 0 or 0.0.)
OUT1 proportional band
(P)
0 to Input span
( )
DC voltage, current input: 0.0 to 1000.0%
(ON/OFF control action when set to 0 or 0.0.)
Integral time (I)
0 to 3600 seconds (Setting the value to 0 disables the function.)
Derivative time (D)
0 to 1800 seconds (Setting the value to 0 disables the function.)
OUT1 proportional cycle
1 to 120 seconds
ARW
0 to 100%
OUT1 ON/OFF
hysteresis
0.1 to 1000.0
( )
DC voltage, current input: 1 to 10000 (The placement of the decimal
point follows the selection.)
OUT1 high limit, low limit
0 to 100% (Direct current output: -5 to 105%)