56
Regency GF950L-2 Gas Fireplace
920-276c
10.29.20
8
. Pull the ECS V module out, remove the jumper connector and discard.
Connect the new power flue wiring harness as shown below to the same
location of where jumper wire was located. Refer to the wiring diagram.
9. Flip DIP switch #2 to the ON position as shown to enable the power flue.
Refer to the table for switch function information.
Jumper Connector
New Wiring Harness
FOR POWER FLUE: SWITCH #2 TO ON POSITION
DIP Switch
Function
Description of Function
1
Convection Fan
control
ON - Convection Fan is
always on if the burner is lit
OFF - Convection Fan is
capable to be switched off
independent of the burner
2
Model Selection
ON - Power Flue mode
OFF - Non-Power Flue mode
3
Gas Type Selection
ON - Natural Gas
OFF - Propane/ULPG
4
Spare
N/A
IMPORTANT: The convection fan must always remain in the ON position.
Do not turn this to the OFF position. 1,2,3 are all shown in ON position.
Note that picture shown is how you would see this when removing this ECS
V control module from appliance.
10. Place the ECS V module back into the appliance in its original location
and screw the front panel plate back into place.
2
GF950 ECS V
Natural Vent to Power Vent Conversion
installation