12
Regency GF950L-2 Gas Fireplace
installation
COMBUSTIBLE REQUIREMENTS
FRAMING & FINISHING (COMBUSTIBLE)
Note:
Depending on the material used for finishing, the nailing strips must
be set accordingly so that the finished material is always be flush
with the edge of the flange.
If finishing with material with a combined thickness greater than
19mm, non-combustible material must be used.
Note:
*Finishing Trim or one of the fascias must be used with com-
bustible finishing.
1
0mm to 19mm combustible finishing can be used if the 13mm
air gap around the front facing of the unit is maintained. Finishing
material cannot be thicker than 19mm and must be flush with the
front edge of the flange.
Note:
•
The siding nailing strips are factory set at 10mm. The top nailing
strip is fixed during transit to the rear of the appliance.
•
Do not place any reinforcement in front of header and behind
finishing material.
•
The top nailing strip must be used. It is fixed during transit to
the rear of the unit.
NOTE:
The appliance must be installed on a flat,
solid, continuous surface For example a
wood, metal or concrete floor. In a raised
(on the wall) application the appliance
must be installed on a metal or wood
panel extending the full width and depth
of the appliance.
NOTE:
Do not remove the standoffs which are
located around the perimeter off this unit
These are in place and act as a guide for
the combustible material to be placed.
148mm
470mm
1021mm
618mm
Finished
Material
1
0mm-19mm thick-
ness using combus-
tible finishing
Note: must maintain
13mm air gap all
around
(see diagrams below
and on next page)
1
st
slot
Unit
13mm
gap
NOTE: Maintain a 13mm gap
all round.
A minimum of 10mm to
maximum 19mm material
thickness is required.