Regency GF950L-2 Gas Fireplace
39
installation
FLUEING INTRODUCTION (INLINE POWER FLUE)
The GF950L uses the "balanced flue" technology Co-Axial system. The inner liner flues products of combustion to the outside while the outer liner draws
outside combustion air into the combustion chamber thereby eliminating the need to use heated room air for combustion and losing warm room air up the chimney.
Note: These flue pipes must not be connected to any other appliance.
The gas appliance and flue system must be vented directly to the outside of the building, and never be attached to a chimney serving a separate solid fuel or
gas burning appliance. Each direct vent gas appliance must use it's own separate flue system. Common flue systems are prohibited.
IMPORTANT:The inline power flue must be installed within the confines of the home/structure and must be accessible for future servicing. An access hole as
noted in this manual or an attic space would be suitable.
FLUEING ARRANGEMENTS FOR HORIZONTAL TERMINATIONS
INLINE HORIZONTAL FLUE CHART
FLUE RESTRICTOR POSITION
Inline Power Flue Bypass Setting:
25.4 mm
Burner Aeration Setting:
NG: 4.4mm
Propane: 11mm
ULPG: 13mm
920-210
0
3
.2
4
.20
1
GF950
PV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Venting Arrangements for Horizontal Terminations
Inline Horizontal Vent Chart
Note: Rigid pipe is approved for up to
60
feet
(18m)
.
Note: Flex pipe is approved for up to 40 feet
(12m) u
sing 2 X 946-756
- 20 foot
(6m) f
lex kits.
The gas power vent system is designed to allow the installation of a gas appliance when typical
natural
vent configurations (shown in this manual)
are not possible.
Vent Restrictor Position
318"
238"
138"
Inline power vent location restrictions:
Minimum 4 ft (1.2 m) from the unit
Minimum 1 ft (0.3 m) prior to an elbow.
Minimum 1 ft (0.3 m) following an elbow.
Minimum 1 ft (0.3 m) prior to a termination cap.
When the inline blower is installed after a negative run, for every foot of
negative run the inline blower must be an equal distance or greater from the
90-degree elbow. See example above.
Minimum 1 ft (0.3 m)
following an elbow
Minimum 1 ft (0.3 m)
prior to a termination
cap
Minimum 1 ft (0.3 m)
prior to an elbow
Minimum 4 ft (1.2 m)
from the unit
Important:
Maximum total vent length =
60
'
(18m)
maximum of six - 90° elbows
permitted.
One 90° elbow = two 45° elbows.
Maximum total negative vent length = 7'
(2m)
.
Note: Maximum length of
60
feet
(18m)
is based on overall length of
combined chimney components.
Do not run positive venting after a negative run.
Restrictor -
Set 3 - 18mm open
Maximum allowable negative run 7 ft (2.1 m)
**
Inline blower when installed after a negative
run must be an equal distance or greater from a
90 degree elbow. (Example: In a 3-foot
(0.9m)
negative run, the inline power vent must be a
minimum of 3 feet
(0.9m)
away from the elbow.)
60
'
(18m)
Overall length
Max.
Shown with 5 - 90
0
elbows
60
'
(18m)
Overall length
Max.
Shown with 3 - 90
0
elbows
60
'
(18m)
Run (no rise)
Note: Rigid pipe is approved for up to 18m.
Note: Flex pipe is approved up to 12m using 2x946-756 - 6m flex kits.
The gas power flue system is designed to allow the installation of a gas applianace when typical natural flue configurations (shown in this manual) are not
possible.
Inline power flue location restrictions:
Minimum 1.2 m from the unit
Minimum 0.3 m prior to an elbow.
Minimum 0.3 m following an elbow.
Minimum 0.3 m prior to a termination cap.
When the inline blower is installed after a negative run, for every foot of
negative run the inline blower must be an equal distance or greater from the
90-degree elbow. See example above.
Minimum 0.3m
following an elbow
Minimum 0.3 m
prior to a termination
cap
Minimum 0.3 m
prior to an elbow
Minimum 1.2m
from the unit
Important:
Maximum total flue length = 18m maximum of six - 90° elbows permitted.
One 90° elbow = two 45° elbows.
Maximum total negative flue length = 2.1m.
Minimum 1.8 m rise from top of appliance if there is a negative run.
Note: Maximum length of 18 meters is based on overall length of com-
bined chimney components.
Do not run positive flueing after a negative run.
Restrictor - Set 3 - 18mm open
Maximum allowable negative run 2.1m
**Inline blower when installed after a negative
run must be an equal distance or greater
from a 90 degree elbow. (Example: In a 0.9m
negative run, the inline power flue must be a
minimum of 0.9m away from the elbow.)
18m Overall length Max.
Shown with 5 - 90
0
elbows
18m Overall length Max.
Shown with 3 - 90
0
elbows
18m Run (no rise)
NOTE: Ensure aeration is set to correct configura-
tion.
Minimum 1.8 m rise from top of appliance if there is a negative run
Содержание Greenfire GF950L Series
Страница 93: ...Regency GF950L 2 Gas Fireplace 93 NOTES notes ...
Страница 100: ......
Страница 101: ...Regency GF950L 2 Gas Fireplace 101 NOTES notes ...
Страница 102: ...102 Regency GF950L 2 Gas Fireplace NOTES notes ...
Страница 103: ......