66
Regency GF950L-2 Gas Fireplace
installation
AERATION ADJUSTMENT
The burner aeration is factory set but may need adjusting due to either the
local gas supply or altitude. Open the air shutter for a blue flame or close for
a more yellow flame.
Minimum Air Shutter Opening for Natural Flue:
NG 9.5 mm
Propane 13 mm
ULPG Full Open
Note: Any damage due to carboning resulting from improperly setting
the aeration controls is NOT covered under warranty.
Minimum Air Shutter Opening for Power Flue:
NG 4.4 mm
Propane 11 mm
ULPG 13 mm
Note: Ensure aeration is set to correct configuration.
845 S.I.T. VALVE
DESCRIPTION
1) On-Off Solenoid Valve EV1
2) On-Off Solenoid Valve EV2
3) Inlet Pressure Test Point
4) Outlet Pressure Test Point
5) Connection for Pressure Regulator/Combustion
Chamber Compensation
6) Pressure Regulator for Minimum and Maximum
Outlet Pressure
7) Gas Outlet Pressure Electric Modulator
8) Pilot Outlet
9) Main Gas Outlet