Regency GF950L-2 Gas Fireplace
HORIZONTAL TERMINATIONS - INLINE POWER FLUE
RIGID PIPE 102MM X 168MM
920-210
02.20.20
6
GF950
PV
Inline Power Vent Vertical or Horizontal Installation Instructions
Horizontal Terminations - Inline Power
Flue
Rigid Pipe 4" x 6
-5/8"
(102mm x 168mm)
The minimum components required for a basic horizontal
termination are:
1 Horizontal Termination Cap
1 Power
Flue
Kit
1 Rigid Pipe Adaptor
1 Length of pipe to suit wall thickness and total
flue
run
(see Table 1)
Adjustable pipe lengths/slips
Wall thickness is measured from the back standoffs to the inside
mounting surface of termination cap. Create a level surface to mount the
vent terminal. The Terminal must not be recessed into siding. Measure
the wall thickness.
Flat Wall Installation
Wall Thickness
(
mm
)
Flue
Length Required
(
mm
)
102mm - 140mm
152mm
178mm
-
216mm
229mm
254mm
-
292mm
305mm
229mm
-
368mm
279mm
-
371mm
Adj. Pipe
381mm
-
597mm
432mm
-
610mm
Adj. Pipe
Pipe Length
Vertical Terminal
Storm Collar
Flashing
Ceiling Firestop
Wall Thimble
o
90 Elbow
Pipe Length
Vent Guard - if required
(Part #946-506/P)
Standoff
Wall Thimble
Pipe Length
Slip Section
Adj. Pipe Length/Slip
Power
Flue
Terminal
Rigid Pipe Adaptor
(TM)
AstroCap
Termination Cap
(Part #946-523/P)
Power Vent Kit (Part
946
-
76
5)
1
51
0-994
Rigid Pipe Adaptor
Sold separately
Amount required
for install
102mm
x
16
8
mm
Rigid Pipe Sold separately
1
666-945
Power Vent Kit
Sold separately
1
946-206
Vinyl Siding Standoff
Sold separately
1
946-523/P
Astro Cap Termination
Sold separately
1
Wall Thimble
Sold separately
1
946-506/P
Vent Guard
Sold separately
NOTE: Slip section is mandatory.
Table 1
Important:
Maximum total
flue
length =
18m
with a maximum of six 90
0
elbows.
One 90
0
elbow = two 45
0
elbows.
Maximum total negative
flue
length =
2.1m
.
Note: Maximum length of
18m
is based on overall length of
combined chimney components.
Do not run positive
flue
ing after a negative run.
Inline power
flue
location restrictions:
Minimum 1.2 m from the unit
Minimum 0.3 m prior to an elbow.
Minimum 0.3 m following an elbow.
Minimum 0.3
m
prior to a termination cap.
Minimum
1.8 m rise from top of unit if there is a negative run.
946-763
(Part #946-765)
(Part #510-994)
920-210
04.01.20
6
CV72EPV / CB72EPV
Inline Power Vent Vertical or Hortizontal Installation Instructions
Horizontal Terminations - Inline Power Vent
Rigid Pipe 4" x 6
-5/8"
The minimum components required for a basic horizontal
termination are:
1 Horizontal Termination Cap
1 Power Vent Kit
1 Rigid Pipe Adaptor
1 Vent Reducer
1 Length of pipe to suit wall thickness and total vent run
(see Table 1)
Adjustable pipe lengths/slips
Wall thickness is measured from the back standoffs to the inside
mounting surface of termination cap. Create a level surface to mount the
vent terminal. The Terminal must not be recessed into siding. Measure
the wall thickness.
Flat Wall Installation
Wall Thickness
(inches)
Vent Length Required
(inches)
4" - 5-1/2"
6"
7" - 8-1/2"
9"
10" - 11-1/2"
12"
9" - 14-1/2'
11" - 14-5/8" Adj. Pipe
15" - 23-1/2"
17" - 24" Adj. Pipe
Pipe Length
Vertical Terminal
Storm Collar
Flashing
Ceiling Firestop
Wall Thimble
o
90 Elbow
Pipe Length
Vent Reducer
(Part #946-606)
Vent Guard - if required
(Part #946-506/P)
Standoff
Wall Thimble
Pipe Length
Slip Section
Adj. Pipe Length/Slip
Power Vent Terminal
Rigid Pipe Adaptor
(TM)
AstroCap
Termination Cap
(Part #946-523/P)
Table 1
Power
Flue
Kit (Part 946-765)
1
510-994
Rigid Pipe Adaptor
Sold separately
Amount required
for install
102mm x 168mm Rigid Pipe
Sold separately
1
946-765
Power Flue Kit
Sold separately
1
946-206
Vinyl Siding Standoff
Sold separately
1
946-523/P
Astro Cap Termination
Sold separately
1
946-763
Wall Thimble
Sold separately
1
946-506/P
Vent Guard
Sold separately
1
911-339
PV Wiring Harness
Included w/Power Flue Kit
NOTE: Slip section is mandatory.
Important:
Maximum total vent length = 72' with a maximum of six 90
0
elbows.
One 90
0
elbow = two 45
0
elbows.
Maximum total negative vent length = 7'.
Note: Maximum length of 72' is based on overall length of combined
chimney components.
Do not run positive venting after a negative run.
Inline power vent location restrictions:
Minimum 4 ft (1.2 m) from the unit
Minimum 1 ft (0.3 m) prior to an elbow.
Minimum 1 ft (0.3 m) following an elbow.
Minimum 1 ft (0.3 m) prior to a termination cap.
Minimum 6 ft (1.8 m) rise from top of unit if there is a negative run.
IMPORTANT:The inline power flue must be installed within the confines of the home/structure and must be accessible for future servicing. An access hole
as noted in this manual or an attic space would be suitable.
installation