Installation and Commissioning
Case Installation
REGATRON
Performance. Precision. Quality.
TC.ACS - Device Manual (V04.60) - 26.4.2022
28 / 66
4.3 Case Installation
The TC.ACS is intended to be installed in a standard 19” switch cabinet with an external air flow. In this case it is to
be placed on rails or shelves and fastened at the holes on the left and right edges of the front panel. Usually M6
screws can be used.
Fig. 8:
Case installation with the help of a trolley
CAUTION
Possible damage!
- Due to soiling and foreign bodies at the installation location
- Due to a build-up of heat
Avoidance:
- The installation location must be free of conductive and aggressive substances as well as
moisture.
- No foreign bodies such as drilling swarf or screws are to be allowed to fall into the system.
- The site conditions (see technical datasheet) must be met.
- The ventilation openings on the front panel and rear wall of the devices must not be
covered or sealed.
Due to the weight of the device the following is to be regarded:
- Rails or shelves must be robust.
- The case for a TC.ACS must be in contact over full installation depth.
- At the rear a cross-member must be installed for additional fastening.