Installation and Commissioning
Electrical Installation
REGATRON
Performance. Precision. Quality.
TC.ACS - Device Manual (V04.60) - 26.4.2022
31 / 66
Grounding cables must have a cross-section area equal to that of the external conductors and with:
•
fixed connection
at least 10 mm
2
•
mobile operation of the device
, the following:
4.4.2.2 Electromagnetic Compatibility of Cables
For electromagnetic compatibility of cables the following must be given:
• Large area earthing (suitable for EMI)
• Shielded cables with shields earthed on both ends
• Star topology earthing (suitable for EMI) of the device
4.4.3 Procedure
To electrically install the TC.ACS, do the following:
Connect the mains via the X10 AC line input terminal (see
).
Connect the load to the X20 AC load output terminal (see
).
Connect the earthing connector (PE) of the X20 AC load output terminal to earth.
Connect the additional earthing stud on the rear of the device (see
) to earth.
Cross-section Area
External Conductors
Grounding Cables
up to 16 mm
2
equal to external conductors
16 mm
2
to 35 mm
2
16 mm
2
35 mm
2
and more
half of external conductors
The system is equipped with interference suppression filters in all power and signal
connections. Correct installation ensures conformity with the applicable standards.