Installation and Commissioning
Site Conditions
REGATRON
Performance. Precision. Quality.
TC.ACS - Device Manual (V04.60) - 26.4.2022
27 / 66
4.2 Site Conditions
CAUTION
Electric surge!
The system is designed for use in LPZ1 (Lightning Protection Zone 1).
CAUTION
Overheating!
Make sure that the warm exhaust air is not drawn back into the system.
Installation conditions
Over voltage category (according to EN 62477-1)
3
Distance at the front
to the nearest wall or large
surface area body
> 850 mm
For access to the front as well as for
drawing in the cooling air
NOTE: If there is a cabinet door, an
escape route of > 600 mm width must
be provided in front of the open door.
This is independent of the 850 mm
distance.
Distance at the rear
to the nearest wall or large
surface area body
> 850 mm
For access to the rear, as well as for
exhaust of the cooling air
NOTE: If there is a cabinet door, an
escape route of > 600 mm width must
be provided behind the open door.
This is independent of the 850 mm
distance.
Environmental conditions
Maximum altitude
2000 meters above sea level
Temperature
-5°C...40°C
Humidity
0...95%
Moisture condition of the skin (according to EN 62477-1)
Dry
Vibrations (according to IEC-60068-2-6)
Test Fc
Pollution degree (according to EN 62477-1)
2
Environmental operating conditions (according to IEC 60721-3-3)
Climate
3K22
Pollution degree
see above
Special climatic conditions
3Z1
Mechanically active substances 3S5
Mechanical
3M11
Biological
3B1