Option: Liquid to Air Heat Exchanger TC.LAE
Installation and Commissioning
REGATRON
Performance. Precision. Quality.
TC.ACS - Device Manual (V04.60) - 26.4.2022
54 / 66
11.3.5 Filling of Cooling Liquid
11.3.5.1 Safety Advice
11.3.5.2 Prereqisites
For the filling of cooling liquid to the cooling circuit the following must be given:
• Both the TC.ACS device and the TC.LAE device are in horizontal position.
• Both the TC.ACS device and the TC.LAE device are switched off.
• The following material is provided:
Regatron AG fill-up kit, including: 2,5 l cooling liquid Antifrogen® N 30%, 1 funnel, 2 hoses with fittings
attached
Collection vessel
Absorbent cloth or paper
6 mm Allen wrench
You can order cooling liquid directly from the retailer Clariant. The product is named
Antifrogen® N 30%.
for
.
WARNING
Possible harm by cooling liquid!
According to the GHS the recommended cooling liquid Antifrogen® N 30% is classified as being
hazardous in the following ways:
- Harmful if swallowed (H302)
- May cause damage to organs through prolonged or repeated exposure (H373)
Avoidance:
When handling with cooling liquid, do the following:
- pay attention to the warning signs on the product.
- open doors and windows and ensure the room is well ventilated also on the ground level.
- use respiratory protection and protective cloves which are resistant against solvents.
- close cooling liquid vessels immediately.
- keep out of the reach of children.
- avoid contact with skin and eyes.
If exposed or concerned: Get medical advice!
CAUTION
Damage of the Device!
A short circuit may occur due to moisture (cooling liquid) in the device.
Avoidance:
- Make sure that both the TC.ACS device and the TC.LAE device are switched off.
- Keep the cooling liquid from spilling on and into the devices.