Mode 3
This mode selection is for hydronic heating systems with
single or multiple heaters (maximum 4 heaters) in primary/
secondary piping configuration with or without Outdoor
Air Reset (S4) with indirect DHW on the heater loop (with
priority). See
Figure 21.
The system temperature is controlled by the Supply Sensor
(S3) whenever the indirect call for heat is
not active. The
DHW Supply Sensor (S5) determines the indirect call/tank
setpoint. During an indirect call for heat the heater firing
rate is determined by the water temperature at the Indirect
Supply Sensor (S6) and the Target Max setting when using
the Indirect DHW sensor (S5).
The Heater/Injection Pump (P1) runs during all heat calls
regardless of priority. The Indirect DHW Pump (P3) runs
during an indirect call for heat with no “Off” delay.
Figure 21.
Mode 3 - Single Heater with Indirect on Heater Loop Primary/Secondary Piping
The Heater/Injection Pump (P1) is delayed “Off” as user-
defined in the Heater menu and the System Pump (P2) is
delayed “Off” in the ADJUST menu.
The System Pump (P2) runs whenever the system is
enabled for heating and the outdoor air temperature
is lower than the warm weather shut down (WWSD)
temperature setting (if utilized) unless an indirect call for
heat is present.
NOTE:
A Tank Aquastat can be used in lieu of the Indirect
DHW Sensor (S5). See VERSA IC Manual (5000.72) for
additional details.
NOTE:
See VERSA IC Manual (5000.72) for more
information on cascade systems.
S1
S2
P2
S4
P1
VERSA
PIM
MODBUS
ENABLE
0-10/4-20mA
S3
1
P3
S5
AQUASTAT
LOCATED IN
OUTLET PIPE
S6
Maximum distance not to exceed
4 pipe diameters or 12" (305 mm)
1
FACTORY INSTALLED SENSOR
FIELD INSTALLED SENSOR
S1a
S2a
P2a
S3a
S1b
S2b
P1b
S1c
S2c
P1c
S1d
S2d
P1d
A
B
C
D
S4a
= FACTORY INSTALLED SENSOR
= FIELD INSTALLED SENSOR
(MASTER)
PIM
VERSA
PIM
VERSA
PIM
VERSA
PIM
VERSA
P1a
S5a
P3a
S6a
MODBUS
0-10/4-20mA
ENABLE
1
AQUASTAT
LOCATED IN
OUTLET PIPE
CONNECT SYSTEM
PUMP IN PARALLEL
FROM EACH CASCADE
FOLLOWER OUTPUT
1
Maximum distance not to exceed
4 pipe diameters or 12" (305 mm)
1
F10629
Figure 22.
Mode 3 - Heater Cascade with Indirect on Heater Loop Primary/Secondary Piping