9
NO MINIMUM
SERVICE CLEARANCE
REQUIRED
30" (762 MM) MIN.
SERVICE CLEARANCE
FRONT VIEW
24" (610 MM) MIN.
SERVICE CLEARANCE
TOP VIEW
F10563
Figure 7. Minimum Clearances from Combustible
Surfaces – Indoor and Outdoor Installations
Clearances
Indoor Installations
Heater Side
Minimum
Clearances from
Combustible
Surfaces
in. (mm)
Minimum Service
Clearance
in. (mm)
Floor *
0
0
Rear
24 (610)
24 (610)
Right Side
0
0
Left Side
0
0
Top
0
0
Front
Open
30 (762)
Vent
1 (25)
1 (25)
* DO NOT install on carpeting
Table G. Clearances - Indoor Installations
For ease of servicing, a clearance of at least 30" (762 mm)
in front, at least 24" (610 mm) on the rear. This will allow
the heater to be serviced in its installed location without
movement or removal of the heater.
Service clearances less than the minimum may require
removal of the heater to service either the heat exchanger
or the burner components. In either case, the heater must
be installed in a manner that will enable the heater to be
serviced without removing any structure around the heater.
Pallet Jack/Forklifting
The XFiire heaters are designed to be moved by pallet jack
or forklift (front side or either side).
Figure 8. Pallet Jack
Figure 9. Forklifting