NECTOR
Page
9
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
INSTALLER WARNINGS
-
Install the appliance in places that respect the degree of protection and keep the box as
intact as possible when drilling for the housing of the cable glands and/or pipe glands.
-
Avoid using multi-pole cables in which conductors connected to inductive and power
loads and signal conductors are present, such as probes and digital inputs.
-
Avoid housing power cables with signal cables (probes and digital inputs) in the same
ducts.
-
Reduce the lengths of the connection cables as much as possible, avoiding that the
wiring takes on the shape of a spiral capable of possible inductive effects on the
electronics.
-
All conductors used in the wiring must be suitably proportionate to support the load they
must supply.
-
If it is necessary to move the probes farther, it is obligatory to use conductors of
appropriate cross-section and in any case not less than 1 mm
2
. Extending or shortening
of the probes could alter the factory calibration; then proceed with verification and
calibration by means of direct comparison with a thermometer that is ACCREDIA tested
and certified.
PACK CONTENTS
The NECTOR electronic controller, for assembly and use, is equipped with:
•
No. 3 Seals, to be interposed between the fixing screw and the bottom of the box.
•
No. 1 User manual.
•
No. 1 NTC 10K 1% black 1.5m probe.
•
No. 1 NTC 10K 1% black 3m probe.
•
No. 1 NTC 10K 1% yellow probe of 3m length.
•
No. 1 Calibration report.
INSTALLATION
2.2
2.1
Содержание NECTOR
Страница 2: ...NECTOR Page 2 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 61: ...NECTOR Page 61 OPERATION AND MAINTENANCE MANUAL Rev 03 21 NECTOR200 CONNECTION DIAGRAM INPUTS OUTPUTS A 2...
Страница 62: ...NECTOR Page 62 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 63: ...NECTOR Page 63 OPERATION AND MAINTENANCE MANUAL Rev 03 21...