OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
EcO
Compressor oil pressure switch protection
insertion:
(the outputs are all deactivated except
for the alarm one, if present).
•
Check the compressor status.
•
Check the compressor protection oil pressure
switch.
•
If the problem persists, contact technical
support.
Ec
Compressor generic protection alarm input
(e.g. thermal protection or maximum pressure
switch).
The outputs are all deactivated except the alarm
one, if present.
•
Check the compressor status.
•
Check compressor absorption.
•
If the problem persists, contact technical
support.
EcA
Compressor alarm
(display only)
•
Check the compressor status.
EFc
Condenser fan alarm
(display only)
•
Check the status of the condenser fans.
EFE
Evaporator fan alarm
(display only)
•
Check the status of the evaporator fans.
ES1
Network connection alarm (Wi-Fi, Ethernet,
Bluetooth)
•
If the problem persists, contact technical
support.