NECTOR
Page
26
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
An2
Presence of evaporator probe 1:
excluding
the
evaporator
probe,
defrosting
occurs
cyclically with period d0 and ends with the
intervention of an external device that closes
the remote defrosting contact or with the expiry
of time d31.
0 = disabled
1 = Evaporator probe 1
0
An4
Probe configuration 4 (NTC)
0 = disabled
1 = defrosting 2
2 = product temperature (reading and recording)
0
An5
Probe configuration 5 (4-20 mA)
0 = disabled
1 = humidity probe (adjustment and recording)
2 = humidity probe (alternate reading at room
temperature, adjustment and recording)
3 = high pressure probe (for condenser fan
management, AUx=+/-9)
0
Ao1
0-10V Output configuration
0 = disabled
1 = evaporator fan adjustment (fixed speed FsE)
2 = condenser fan adjustment (requires An5=2)
0
in1
INP-1 digital input setting
16 = Compressor protection, display only (N.O., EcA)
15 = Condenser fan protection, display only (N.O., EFc)
14 = Evaporator fan protection, display only (N.O., EFE)
13 = Oil pressure switch protection (N.O., EcO)
12 = Minimum pressure switch protection (N.O., EcL)
11 = Maximum pressure switch protection (N.O., EcH)
10 = Pressure switch protection (N.O., EcP)
9 = Compressor thermal protection (N.O., Ect)
8 = Night input (energy saving) (N.O.)
7 = Remote defrost stop (N.O., active on the ascent front)
6 = Start defrosting remotely (N.O., active on the ascent front)
5 = Remote standby (N.O.) To indicate the remote standby OFF is
displayed on the display
4 = Pump-down pressure switch (N.O.) (see Chap. 5.27)
3 = Man in Cell alarm (N.O.)
2 = Compressor protection (N.O.)
1 = Door switch (N.O.)
0 = disabled
-1 = Door switch (N.C.)
-2 = Compressor protection (N.C.)
-3 = Man in Cell Alarm (N.C.)
-4 = Pump-down pressure switch (N.C.) (see Chap. 5.27)
-5 = Remote Stand-by (N.C.) To indicate the remote standby OFF
is displayed on the display
-6 = Start defrost remotely (N.C., active on the descent front)
-7 = Stop defrost remotely (N.C., active on the descent front)
-8 = Night input (energy saving) (N.C.)
-9 = Compressor thermal protection (N.C., Ect)
-10 = Pressure switch protection (N.C., EcP)
-11 = Maximum pressure switch protection (N.C., EcH)
-12 = Minimum pressure switch protection (N.C., EcL)
-13 = Oil pressure switch protection (N.C., EcO)
-14 = Evaporator fan protection, display only (N.C., EFE)
-15 = Condenser fan protection, display only (N.C., EFc)
-16 = Compressor protection, display only (N.C., EcA)
1
in2
INP-2 digital input setting
- Same legend in1 values -
2
in3
INP-3 digital input setting
- Same legend in1 values -
3
in4
INP-4 digital input setting
- Same legend in1 values -
4
in5
INP-5 digital input setting
- Same legend in1 values -
5
Содержание NECTOR
Страница 2: ...NECTOR Page 2 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 61: ...NECTOR Page 61 OPERATION AND MAINTENANCE MANUAL Rev 03 21 NECTOR200 CONNECTION DIAGRAM INPUTS OUTPUTS A 2...
Страница 62: ...NECTOR Page 62 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 63: ...NECTOR Page 63 OPERATION AND MAINTENANCE MANUAL Rev 03 21...