CELL DOOR SWITCH MANAGEMENT
Parameters: doC (2°), Tdo (2°).
When the door switch is opened, the evaporator fans turn off and the compressor will continue to
operate for the
doC
time, after which it will turn off. After the tdo time, normal operation of the
control is restored by giving the
“open door” alarm signal (Ed). It is always possible to switch the
light off or on manually using the light button
, regardless of the status of the door switch.
HUMIDIFICATION MANAGEMENT
Parameters: Au1/2 (3°), StU (2°), r1 (2°).
The
NECTOR
controller activates the humidity call when the ambient humidity drops below the set
value
StU
minus the differential
r1
; it disengages the humidity call when the ambient humidity
exceeds the set value. Configure Au1/2 = +/- 7 to enable a digital output as humidification consent.
5.32
5.33
Fans
Compressor
Open
door
Closed
door
Door switch