NECTOR
Page
23
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
AtE
Temperature alarm enabling
0 = always enabled
1 = disabled in case of standby
2 = disabled if door switch active
3 = disabled if standby or door switch
active
0
C1
Minimum time between shutdown and next
compressor power on.
0 ÷ 15 minutes
0 = disabled
0 min
CE1
Compressor ON operating time in case of faulty
ambient probe
(emergency operation).
With CE1=0, the emergency operation remains
disabled in the presence of error E0: the compressor
remains off and defrosting is inhibited to preserve
the residual cold.
0 ÷ 240 min
0 = deactivated
0 min
CE2
Compressor OFF operating time in case of faulty
ambient probe
(emergency operation).
5 ÷ 240 min
5 min
doC
Compressor guard time for door switch:
when
the door switch is opened, the evaporator fans turn
off and the compressor will continue to run for
the
doC
time, after which it will turn off.
0 ÷ 15 minutes
0 = disabled
0
tdo
Compressor reset time after opening the door:
when the microdoor is opened and after the time
tdo, normal operation of the control is restored by
signalling the
“open door” alarm
Ed
.
0 ÷ 240 minutes
0 = disabled
0
tLo
Cell light alarm signal and display delay time:
when the light comes on with the key and after the
time tLo, the
E9
alarm is activated. If it is silenced
and the light is not switched off upon the new expiry
of the time tLo, the alarm reappears.
0 ÷ 240 minutes
0 = disabled
0
Fst
Fan block temperature
The fans will remain stationary if the temperature
value read by the
evaporator
probe is higher than
the value of this parameter.
-45 ÷ +99°C
+99°C
Fd
Differential for Fst
+1 ÷ +10°C
+2°C
LSE
Minimum value attributable to the set-point
-45 ÷ (HSE-1) °C
-45°C
HSE
Maximum value attributable to the set-point
(LSE+1) ÷ 99 °C
+99°C
dnE
Enable day/night (energy saving)
During night operation the decimal point flashes.
0 = disabled
1 = enabled
0
nSC
SETPOINT
correction
factor
during
night
operation
(energy saving, with In1 or In2 or In3 = 8
or -8, or tdS/tdE).
During night operation the adjustment Set is:
Adjustment set = Set + nSC
-20.0 ÷ +20.0°C
0.0°C
StA
Temperature set for
auxiliary relay
, anti-
condensation resistance management.
-45 ÷ +99°C
0°C
StU
Humidity set
0 ÷ 100 %
0
r1
Humidity differential
1 ÷ 20 %
5
FsE
Evaporator fan speed, only if Ao1=1
20 ÷ 100 %
100 %