NECTOR
Page
27
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
in6
INP-6 digital input setting
- Same legend in1 values -
6
in7
INP-7 digital input setting
- Same legend in1 values -
7
AU1
Relay management
alarm/auxiliary 1
11 = defrost output 2 (N.O.)
10 = active night mode (N.O.)
9 = condenser fan consent (N.O., managed if An5=2,
high pressure probe)
8 = liquid solenoid (N.O., for hot gas defrosting
management)
7 = humidify call, only if An5=1 (N.O.)
6 = hot call (N.O.)
5 = relay energised during standby (N.O.)
4 = energised with compressor output energised. Used
for condensing units. (N.O.)
3 = pump-down function (N.O.) (see Chap. 5.27)
2 = automatic auxiliary relay managed by temperature
set StA with differential 2°C (N.O.)
1 = relay energised in presence of alarm (N.O.)
0 = disabled
-1 = relay de-energised in presence of alarm (N.C.)
-2 = automatic auxiliary relay managed by temperature
set StA with differential 2°C (N.C.)
-3 = pump-down function (N.C.) (see Chap. 5.27)
-4 = relay de-energised with compressor output
energised. Used for casing resistance. (N.C.)
-5 = relay de-energised during standby (N.C.)
-6 = hot call (N.C.)
-7 = humidification call (N.C.), only if An5=1
-8 = liquid solenoid (N.C., for hot gas defrosting
management)
-9 = condenser fan consent (N.C., managed if An5=2,
high pressure probe)
-10 = active night mode (N.C.)
-11 = defrost output 2 (NC)
-1
AU2
Relay management
alarm/auxiliary 2
- Same legend AU1 values -
4
cE
Network connection type
0 = Ethernet
1 = Wifi
0
cB
Bluetooth Management
0 = Bluetooth disabled
1 = Bluetooth activatable
1
cCL
Cloud management
0 = disabled
1 = active (data submission only)
1
cSL
Local web server management
0 = disabled
1 = active (data display only)
2 = active (data display and command reception)
2
P1
Password: protection type.
Active when PA is other than 0 (see Chap.
5.28).
0 = Displays only the set point and allows
alarm silencing. Blocks all other functions.
1 = Displays set point, access to light buttons,
defrosting and silent alarms
2 = Blocks access in first, second and third
level programming
3 = Blocks access in second and third level
programming
3
PA
Password.
(see P1 for type of protection).
0...999
0 = Function disabled
0