NECTOR
Page
24
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
StP
Condenser fan pressure set
-0.5 ÷ 90.0 Bar
0
r2
Differential condenser fan pressure SET.
Value
always above the value of (iOv)
0.6
5.0 Bar
2.0 Bar
iOv
Fan inverter offset
(pressure)
0.5
2.5 bar
always < r2
0.5 Bar
iLv
Fan inverter: setting the minimum value of the
0-10V output
0.0
10.0 V
3.0 V
iHv
Fan inverter: setting the maximum value of the
0-10V output
0.0
10.0 V
10.0 V
bOv
Fan boost:
time for which the 0-10V output of the
fans is forced to 100% (iHv). This is used to obtain
the starting point at their start.
0
240 sec
2 sec
int
Temperature recording range.
Set the time range between one recording and the
next.
Set int > 11 to record a year of data.
0 ÷ 60 minutes
if int=0 recording is disabled
0
ASr
Enabling asynchronous logging.
Normal recording takes place with
int
range. In case
of activation/deactivation of a temperature alarm or
of a digital input, an event recording is forced,
regardless of the int parameter.
It is not possible to determine the time duration
of the memory because the number of events
recorded in a year is not known beforehand.
0 = disabled
1 = enabled
0
dy
Day setting
(see Chap. 5.26)
1 ÷ 31
1
Mo
Month setting
(see Chap. 5.26)
1 ÷ 12
1
Yr
Year setting
(see Chap. 5.26)
0 ÷ 99
15
Hr
Time setting
(see Chap. 5.26)
Hour
-
min
Minute setting
(see Chap. 5.26)
Minutes
rE2
Secondary software release
## = release
read-only
rEL
Software release:
indicates the software version.
N.B.:
During battery operation, pressing the
"STAND-
BY” key for 5 seconds the controller turns
off.
## = release
read-only