NECTOR
Page
28
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
dEF
Setting the default parameters
Assume a position on the dEF parameter and
press the
+ keys for 10 seconds
to
reset the default parameters.
- - -
- - -
PROBE DISPLAY (
read-only)
To access the probe display level press and hold the DOWN (
) and STANDBY keys for
a few seconds. The variables of this level represent instantaneous reading of the probes
and are therefore not editable.
Select with the (
) key or the (
) key the variable to be displayed. After selecting the
desired variable, it is possible to view its value by pressing the SET key.
To exit the menu, press and hold the (
) and (
) keys for a few seconds until the cell
temperature value reappears.
PROBE DISPLAY VARIABLES LIST (
read-Only)
VAR.
MEANING
VALUES
DEFAULT
S1
Probe 1 display, ambient temperature
< °C >
-45.0 ÷ +99.0°C
read-only
S2
Probe 2 display, evaporator 1 temperature
< °C >
(displays‘ --- ‘ if An2 =0)
-45.0 ÷ +99.0°C
read-only
S3
Probe 3 display, ambient temperature datalogger
recording probe.
< °C >
(displays‘ --- ’ if Enr =0)
-45.0 ÷ +99.0°C
read-only
S4
Probe display 4
< °C >
(displays‘ --- ’ if An4=0;
evaporator probe temperature 2,
if An4=1;
product probe temperature,
if An4=2)
-45.0 ÷ +99.0°C
read-only
S5
Probe display 5
< HR% or Bar >
(
displays‘ --- ’ if An5=0;
humidity probe,
if An5=1;
pressure probe,
if An5=2)
0 ÷ 100 HR%
EP4 ÷ EP2 Bar
read-only
o1
Output value 0-10Vdc
< V >
0.0-10.0 Vdc
read-only
BAt
Backup battery status
No mains power supply:
Level 0 ... 100 %
Mains power supply present:
0 = battery disconnected or
broken
1 = battery charging
2 = battery charged
read-only
5.13
5.14