NECTOR
Page
29
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
DATA LOGGING
To start recordings set int
0
Recordings occur in the intervals established by the
int
parameter, or in case of events if ASr = 1.
The information recorded is:
•
Ambient temperature (IN_1)
•
Evaporator temperature (IN_2)
•
Datalogger probe temperature (IN_3)
•
Probe temperature configurable via An4 (IN_4)
•
Probe pressure / humidity configurable via An5 (IN_12)
•
Min or max temperature alarm on ambient probes and datalogger
•
Standby status
•
Probe configuration (parameters An2, Enr, An4, An5)
•
Switching on the device
•
Digital input status 1 (IN_5)
•
Digital input status 2 (IN_6)
•
Digital input status 3 (IN_7)
•
Digital input status 4 (IN_8)
•
Digital input status 5 (IN_9)
•
Digital input status 6 (IN_10)
•
Digital input status 7 (IN_11)
•
Absence of power
(battery operated)
The advance of date and time entails the deletion of data after the new set date (in the case of
data export to the Telenet).
Note:
Set int > 7 minutes to obtain one year of recordings.
SAVING DATA TO USB
Through the TeleNET program it is possible to store, consult, view graphs and to print quickly and
easily the data downloaded from the NECTOR panels. Alternatively, it is possible to download all
the data stored in the NECTOR EXPERT in standard comma-separated values (CSV) format that
can be viewed on PC with any spreadsheet.
To save internal memory data to the USB device it is necessary to:
1. Use USB memory models (USB stick, USB-SD adapter, etc.) formatted
as FAT32
.
2. Insert the USB stick into the slot on the front panel.
3. Press the key
for 5 seconds.
4. Select the type of export (move with the (
) and (
) keys):
-
No:
exits the save level.
5.15
5.16
Содержание NECTOR
Страница 2: ...NECTOR Page 2 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 61: ...NECTOR Page 61 OPERATION AND MAINTENANCE MANUAL Rev 03 21 NECTOR200 CONNECTION DIAGRAM INPUTS OUTPUTS A 2...
Страница 62: ...NECTOR Page 62 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 63: ...NECTOR Page 63 OPERATION AND MAINTENANCE MANUAL Rev 03 21...