1st LEVEL OF PROGRAMMING
(User level)
To access the first level configuration menu you must:
1. Press and hold the (
) and (
) keys simultaneously for a few seconds until the first
programming variable appears on the display.
2. Release the (
) and (
) keys.
3. Select with the (
) key or the (
) key the variable to be modified.
4. After selecting the desired variable you will be able to:
•
Display the setting by pressing the
SET
key.
•
Change the setting by holding down the
SET
key and pressing one of the (
) or (
)
keys.
5. Once the configuration values have been set, to leave the menu, press and hold the
(
) and (
) keys for a few seconds until the cell temperature value reappears.
Changes made to the variables will be automatically saved when leaving the configuration
menu.
1st LEVEL VARIABLES LIST
(User level)
VAR.
MEANING
VALUES
DEFAULT
r0
Temperature differential
referring to the main SET-POINT.
0.2 ÷ 10.0°C
2.0°C
d0
Defrost interval
(hours)
0 ÷ 24 hours
0 = disabled
4
dd2
Delay to start defrosting on the second evaporator
.
Defrosting of the second evaporator starts dd2 seconds after
the end of defrosting 1. This avoids overloading of the
electrical system during defrosting if limited power is available.
With dd2=0 defrosts 1 and 2 start simultaneously. dd2 is
forced to 0 if d1 = 1 (cycle reversal defrost).
0 ÷ 10 sec
0 = simultaneous start
10 sec
d21
Evaporator 1 defrost end point
.
Defrosting 1 is not performed if the temperature read by the
defrosting probe 1 is higher than the value d21 (in case of a
faulty probe defrosting is performed on time).
-35 ÷ 45°C
15°C
d22
Evaporator 2 defrost end point
.
Defrosting 2 is not performed if the temperature read by the
defrosting probe 2 is higher than the value d21 (in case of a
faulty probe defrosting is performed on time).
-35 ÷ 45°C
15°C
d31
Maximum evaporator defrost duration 1
(minutes)
1 ÷ 240 min
25 min
d32
Maximum evaporator defrost duration 2
(minutes)
1 ÷ 240 min
25 min
5.7
5.8
Содержание NECTOR
Страница 2: ...NECTOR Page 2 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 61: ...NECTOR Page 61 OPERATION AND MAINTENANCE MANUAL Rev 03 21 NECTOR200 CONNECTION DIAGRAM INPUTS OUTPUTS A 2...
Страница 62: ...NECTOR Page 62 OPERATION AND MAINTENANCE MANUAL Rev 03 21...
Страница 63: ...NECTOR Page 63 OPERATION AND MAINTENANCE MANUAL Rev 03 21...