NECTOR
Page
32
OPERATION AND MAINTENANCE MANUAL
Rev. 03-21
COLUMN DESCRIPTION
DATES
: Date of recording
TIME
: Time of recording
PROBE1 (0.1°C)
: Ambient probe temperature (IN_1)
PROBE2 (0.1°C)
: Evaporator probe temperature (IN_2)
PROBE3 (0.1°C)
: Datalogger probe temperature (IN_3)
PROBE4 (0.1°C)
: Probe temperature configurable with An4 (IN_4)
PROBE5 (0.1Bar/RH%)
: Relative probe pressure/humidity configurable with An5 (IN_12)
EL1
: low ambient temperature alarm
EH1
: high ambient temperature alarm
EL3
: Datalogger low temperature alarm
EH3
: Datalogger high temperature alarm
STAND-BY
: Stand-by system
An2=1:
evaporator probe enabled on PROBE2 (IN_2)
Enr=1:
datalogger probe enabled on PROBE3 (IN_3)
An4=1:
evaporator probe 2 enabled on PROBE4 (IN_5)
An4=2:
product probe enabled on PROBE4 (IN_5)
An5=1/2:
humidity probe enabled on PROBE5 (IN_12)
An5=3:
pressure probe enabled on PROBE5 (IN_12)
POWER-ON
: start of the NECTOR (recording performed asynchronously, regardless of the parameter 'int’: in this
way it is possible to understand when the power returns).
DI1
: Digital input DI1 active (IN_5)
DI2
: Digital input DI2 active (IN_6)
DI3
: Digital input DI3 active (IN_7)
DI4
: Digital input DI4 active (IN_8)
DI5
: Digital input DI5 active (IN_9)
DI6
: Digital input DI6 active (IN_10)
DI7
: Digital input DI7 active (IN_11)
BATTERY
: Battery operated. If BATTERY=1 is out of mains power; the controller continues to record temperature
trends for approximately 40 hours (with battery present and charged).