Appendix (Check Points in Installing UM Series)
PACD011001G2 / PACD011004G3
86
Urban Multi Inverter “MX1” Series
2. Header branch pipes
If the selected field pipe differs from the branch pipe in size, cut the connection with a pipe cutter as
shown below.
Fit a stop end on all open branch pipe connections not in use.
Install the branch pipe horizontally.
Insulate the branch pipe as described in the kit installation manual.
Notes:
Install the Line branch pipes horizontally or vertically, keeping it sithin a 30 angle when installed
horizontally.
Install the Header branch pipes so that it branches horizontally.
Do not used a T-joint for the branch pipe.