7. Bad Examples and Good Examples in Installation
7.1
Example 1:
Signal interference due to use of multiple core cable
(all model)
Situation
Although for the purposes of group control there are only 2 units per group there are transmission
malfunctions between the indoor units and the remote controller and the remote controller’s address
display is showing non-existent addresses such as 13 or 15.
Source of Problem
and Remedial
Action
Multiple core cable has been used for at least part of the interconnecting wiring between the remote
controller and the indoor units.
This has resulted in signal interference leading to a transmission malfunction.
The multiple core cable was replaced by twin core cable and the fault disappeared.
Main Points
Although twin core cable had been run from each unit, multiple core cable was used on the way.
In schools, etc., because remote controllers are often installed in a single first floor control room, it is
easier to use a multi-core cable.
Signal interference can result in non-existent addresses appearing on the display.
Содержание Urban Multi MX1 Series
Страница 34: ...Installation 1 PACD011001G2 PACD011004G3 34 Urban Multi Inverter MX1 Series Ceiling Type CS TM ...
Страница 54: ...Installation 1 PACD011001G2 PACD011004G3 54 Urban Multi Inverter MX1 Series ...
Страница 102: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 102 Urban Multi Inverter MX1 Series ...
Страница 103: ...PACD011001G2 PACD011004G3 Appendix Check Points in Installing UM Series Urban Multi Inverter MX1 Series 103 1 ...
Страница 104: ...Appendix Check Points in Installing UM Series PACD011001G2 PACD011004G3 104 Urban Multi Inverter MX1 Series ...